Регистрация
deal.by
AS-Interface sensor/actuator module VBA-2E2A-G12-ZEJ/EA2L - фото 1 - id-p93678006
Характеристики и описание

Техническая спецификация в PDF  

Описание оборудования

G12 flat module
2 inputs (PNP) and 2electronic outputs

General specifications

Slave typeA/B slave
AS-Interface specificationV3.0
Required master specification? V2.1
UL File NumberE223772

Functional safety related parameters

MTTFd270 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %

Indicators/operating means

LED FAULTerror display; LED red
red: communication error or address is 0
red flashing: overload of sensor power supply or outputs
LED PWRAS-Interface voltage; green LED
green: voltage OK
flashing green: address 0
LED AUXext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
LED INswitching state (input); 2 LED yellow
LED OUTSwitching status (output); 2 yellow/red LEDs
Yellow: output active
Red: output overload

Electrical specifications

Auxiliary voltage (output)24 V DC ± 15 % PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current? 40 mA (without sensors) / max. 240 mA
Protection classIII
Surge protectionUAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) derived from mains up to 300 V AC line-to-neutral

Input

Number/Type2 inputs for 2- or 3-wire sensors (PNP), DC
Supplyfrom AS-Interface
Voltage21 ... 31 V
Current loading capacity? 200 mA, overload and short-circuit protected
Input current? 8 mA (limited internally)
Switching pointaccording to DIN EN 61131-2 (Type 2)
Signal delay< 1 ms (input/AS-Interface)

Output

Number/Type2 electronic outputs, PNP overload and short-circuit proof
Supplyfrom external auxiliary voltage UAUX
Current2 A per output
4 A total (TB ? 40 °C)
3 A total (TB ? 70 °C)
Voltage? (UAUX - 0.5 V)

Directive conformity

Electromagnetic compatibility

Standard conformity

Degree of protectionEN60529:2000
Fieldbus standardEN62026-2:2013
InputEN 61131-2
Emitted interferenceEN61000-6-4:2007
AS-InterfaceEN62026-2:2013
Noise immunityEN61000-6-2:2005 , EN62026-2:2013

Programming instructions

ProfileS-B.A.2
IO codeB
ID codeA
ID1 code7
ID2 code2
Data bits (function via AS-Interface) input output
Parameter bits (programmable via AS-i)function

Ambient conditions

Был online: Давно
OOO "ФилФар Технолоджи"
Рейтинг не сформирован
10 лет на Deal.by

AS-Interface sensor/actuator module VBA-2E2A-G12-ZEJ/EA2L

Под заказ
Цену уточняйте
Доставка
Оплата и гарантии