General specifications | |
---|---|
Signal type | Analog input/analog output |
Functional safety related parameters | |
Safety Integrity Level (SIL) | SIL 2 |
Supply | |
Connection | SL1: 1a(-), 1b(-); 2a(+), 2b(+) |
Rated voltage | 20.4 ... 30 V DC bus powered via Termination Board |
Ripple | ? 10 % |
Rated current | 140 mA at 24 V and 20 mA |
Power dissipation | ? 1.8 W at 20 mA |
Power consumption | ? 3.3 W at 20 mA |
Control circuit | |
Connection | SL1: 8a(+), 7a(-); 10a(+), 9a(-); 9b(+), 10b(-); 8b(+), 7b(-) |
Voltage drop | approx. 6 V or internal resistance 300? at 20 mA |
Ripple | 200 mV eff |
Input | |
Output | |
Field circuit | |
Connection | SL2: 5a(+), 5b(-); 1a(+), 1b(-); 3a(+), 3b(-); 7a(+), 7b(-) |
Voltage | ? 15 V at 20 mA |
Input | |
Output | |
Transfer characteristics | |
Deviation | ? ± 0.2 % incl. non-linearity and hysteresis (sink mode 4 ... 20 mA) |
Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) |
Rise time | 10 to 90 % ? 20 ms |
Indicators/settings | |
Display elements | LED |
Control elements | DIP-switch potentiometer |
Configuration | via DIP switches via potentiometer |
Labeling | space for labeling at the front |
Directive conformity | |
Electromagnetic compatibility | |
Conformity | |
Electromagnetic compatibility | NE 21:2006 For further information see system description. |
Degree of protection | IEC 60529 |
Ambient conditions | |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications | |
Degree of protection | IP20 |
Mass | approx. 140 g |
Dimensions | 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch) |
Mounting | on Termination Board |
Data for application in connection with hazardous areas | |
EU-Type Examination Certificate | CESI 02 ATEX 086 |
Certificate | PF 11 CERT 2109 X |
Directive conformity | |
International approvals | |
IECEx approval | IECEx TUN 04.0012 |
8 |